Liquid Caustic Soda Storage Tank Use and Maintenance

Nov 19, 2025

Leave a message

After the liquid caustic soda storage tank is put into use, operating procedures and a maintenance plan must be established. Operators should be trained and certified, and familiar with the properties of liquid caustic soda and emergency handling procedures. During daily operation, record liquid level, temperature, and pressure data, and investigate any abnormalities promptly. Regularly inspect the tank for corrosion, measure wall thickness, and assess its remaining service life. The anti-corrosion coating should be inspected every three to five years, and reapplied if necessary. Safety valves and instruments should be calibrated periodically to ensure accuracy and reliability. When cleaning the storage tank, first drain the liquid caustic soda, rinse with water until neutral, then ventilate and test for combustible gases and oxygen concentration. Entry is only permitted after the tests are satisfactory. Maintenance records should be archived and kept as a basis for equipment management.

 