The following aspects should be emphasized in tank maintenance:
1. Visual Inspection: Regularly check for tank deformation, cracks (deep > 1mm require repair), and corrosion (corrosion rate < 0.1mm/year) to avoid structural hazards;
2. Sealing Test: Use 0.4MPa pressure to test sealing performance, ensuring a leakage rate < 0.5%/h to prevent VOCs volatilization (reducing CO₂ emissions) and the risk of combustion and explosion;
3. Instrument Calibration: Level gauge error must be < ±2%, and safety valve opening pressure deviation < 5% to ensure accurate control of process parameters;
4. Environmental Management: Flammable materials are prohibited within 5 meters of the tank area. Anti-corrosion coatings must meet acid and alkali resistance standards (pH 2-12) to extend service life to over 15 years.